Honeywell C6097 Diaphragm-Actuated Safety Limit Pressure Switches

Cut costs and improve reliability with Honeywell C6097 gas and air pressure limiting switches. Their compact design and easy connections reduce the need for conventional piping and threading operations. C6097 series switches can help reduce your inventory, because they can be used with older, stand-alone compenent valves as well as newer valves.

These safety limit pressure switches can be used in positive- or differential-pressure systems to sense natural gas, liquid propane (LP) gas, or air. C6097A switches break the circuit on pressure fall. C6097B switches break on pressure rise. Models are available with either manual or automatic reset.

 

  • Diaphragm-actuated safety limit switches
  • Available ranges: 0.4—5" WC, 3—21" WC, 12—60" WC or 1.5—7 PSI
  • IP54 enclosure with removable transparent cover protects scale plate and adjusting knob, 1/4" NPT mount
  • Switch ratings: 3.0 AFL, 18.0 ALR, 5.0 Amps resistive; Switch can be wired to turn on alarms
  • UL listed, CSA listed, FM approved, IRI acceptable
  • Operating temperature range: -40° to 140°F

 

Type Description Size
 Catalog Section: Analytical Instruments and Systems Combustion and Flame Safety Solutions Catalog 3.7MB
Honeywell Smart Sensors and Analytical Instruments Brochure Popular Honeywell Burner and Boiler Control (Flame Safeguard) 456KB
Honeywell 7758 Pipeline Electrode Mounting for Industrial pH-ORP Specification Honeywell Mercury-Free Limits and Controls for Commercial and Industrial Combustion Brochure 405KB
Honeywell 7758 Pipeline Bushing Mounting for Meredian Model Selection Guide Honeywell C6097 Gas and Air Pressure Switches Brochure 399KB
Honeywell 7758D Pipeline Electrode Mount with Cap Adapter Model Selection Guide Honeywell C6097 Gas and Air Pressure Switches Specification and Installation Guide 1MB
Honeywell 7758 Pipeline Electrode Mounting Assembly Product Manual Honeywell Whitepaper: Requirements on Connecting a Vent Pipe to a C6097A or C6097B Pressure Switch 1MB

 

Model selection guide:

 
Break Action
Operating RangePressure Differential
at Min. Setpoint
Pressure Differential
at Max. Setpoint
Switch OperationPressure
Connection
 
Mounting
Catalog Number
On Pressure Fall0.4" to 5" WC0.6" WC0.25" WCManual Reset1/8" NPT1/4" NPT C6097A1095
0.4" to 5" WCAuto Recycle1/8" NPT1/4" NPT C6097A1004
3" to 21" WCAuto Recycle1/8" NPT1/4" NPT C6097A1053
12" to 60" WCAuto Recycle1/8" NPT1/4" NPT C6097A1079
On Pressure Rise3" to 21" WC2.4" WC4.2" WCManual Reset1/8" NPT1/4" NPT C6097B1028
12" to 60" WC10" WC12" WCManual Reset1/8" NPT1/4" NPT C6097B1002
1.5 to 7 PSI1.1" WC1.4" WCManual Reset1/8" NPT1/4" NPT C6097B1051
1.5 to 7 PSIAuto Recycle1/8" NPT1/4" NPT C6097B1101