Honeywell RM7840 Microprocessor-Based Programming Control
Models Available to Buy | |
If the model you need isn't listed here, us. | |
Programming control with valve proving. 4- or 10-second pilot flame establishing period, 10-, 15-, 30-second or intermittent main flame establishing period. Running and low-fire interlocks. | RM7840G1022 |
Programming control with valve proving. 4- or 10-second pilot flame establishing period, 10- or 15-second main flame establishing period. Lockout, low-fire, and high-fire interlocks. | RM7840L1075 |
- Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics, and troubleshooting
- Five LEDs provide sequence information. Power LED blinks fault code on Lockout
- Valve proving feature tests valve seat integrity to detect a leak greater than 0.1% of burner input capacity
- Requires S7800A1142 keyboard to set up valve proving (VPS) and change post-purge time